DIRECT FEEDING*S,YSTEMS. 17
compelling the motors to slow down and work inefficiently,
while if the drop reaches 125 volts or more the motors are
nearly inoperative under heavy loads, although they will
still work if tco great demands are not put upon them. It
is highly undesirable to deal with more than 100 volts loss
under maximum load in a 50ovolt system. By overcom-
pounding the generators these conditions can be much re-
lieved. With the maximum drop limited to twenty per
cent, it is clear that the average drop, with the ordinary
ratios between average and maximum load would have to
be limited to five or at the utmost ten per cent.
T'1c. 48.
If the dynamo be overcompounded, as it should be for
at least the average drop, then the maximum drop will gen-
erally fall within safe limits. It isa common practice to
overcompound ten per cent, i. e., fifty volts, so that even
a total drop of twenty-five per cent will still leave the sys-
tem in fair operative condition.
Coming back now to Fig. 48, we have found that the
system is operative at average load by means of the trolley
wire alone, but should be well re-enforced by feeders to
meet the conditions of heavy load. Since we have found
that feeding at the middle point of A B would give too
much drop even if the loss in the feeder were as small as
five per cent at average load, the next step is to feed at two
points. ‘These should be so chosen, if the load is uniform
along the section, as to be one-half the length of the sec-