78 POWER DISTRIBUTIQN FOR ELECTRIC RAILROADS.
tion apart. eand & (Fig. 48) have this position. No load
can therefore be more than 2500 ft. from a feeder. Now
consider the maximum load of 300 amperes at A. Sup-
pose first that the feeder H a is to give five per cent drop,
twenty-five volts at average load. 'This average (half the
total average load) is seventy-five amperes. The distance
A H is 4500 ft., the wire therefore must be of area,
13 X 75 X 4500
25
G = == 175,500,
This is best met by a No. ooo wire, which is the nearest
size (167,000 c. m.) and will give less than one per cent
more drop.
With 300 amperes at A the drop in the trolley wires
for 2500 ft. would be thirty six volts. ‘The drop in the
feeder would obviously be a little over a hundred volts,
making a total quite too great, since the overcompound-
ing, unless a special generator be devoted to the feeder in
question responds to the total load on the system and not
fully to the load at A. FEven the gain from the current
path along H B @ will not relieve matters quite enough.
Now we might use a much larger feeder and thus reduce
the drop, but a simpler and cheaper way is to cross tie
both feeders into the trolley lines at ¢. ‘T'his, assuming
both feeders to be of the same size, puts at our disposal from
@ to ¢ no less than 433,000 c. m., with 334,000 c. m. for the
1000 ft. between H and C. 'The total drop will then be
36 + 31 + 12 = 79 less whatever has been gained from
the overcompounding. ‘T'his last depends on the total
load on the system and is consequently indeterminate, It
could hardly however be less than half the full overcom-
pounding, say twenty-five volts, thus giving a net drop of
fifty-four volts at A.
This cross connecting process is a very useful safe-
guard against extreme terminal loads, though if the whole
line is likely to have a heavy distributed load at the same
time, it is better to take a different step as will presently be
shown.