DIRECT FEEDING SYSTEMS. 33
$4630. This cost would have to be doubled to save 21
per cent of the total energy. ‘The annual charge for this,
counting interest and depreciation at ten per cent, would be
$463, nearly $206 for each per cent saved. Now the amount
of power, based on the average amperes, is about 2700 k.w.
hours per day of eighteen hours; the cost of this per year
at two cents per kilowatt hour would be $19,710, of which
one per cent is $197.10, showing that it will not pay to in-
crease the investment in copper.
The art of feeder design is one that calls for great
Jinesse and skilled judgment in assigning the proper values
to the somewhat uncertain maximum loads. It cannot be
reduced to formulee that will be of use in anything save
special and unusual circumstances. The author has in this
chapter, therefore, merely attempted to give the general
principles to be followed and some idea of the mental pro-
cesses by which the final approximation is reached. In
another chapter the special case of long interurban lines
will be considered.